SERIES 4000INTELLIGENT FIRE ALARMCONTROL PANELGENERALCOMMISSIONINGMANUALISSUE 2C( ACCESS CODE 25276 )
Getting Into Programming ModeWhen the Main Panel is powered up it will be necessary to enter the panel programming mode.Familiarize yourself with this
Connecting A PS2 PC Keyboard To The Main PanelCOMMISSIONINGDISPLAYLOOPCARDHEADERLOOPCARD HEADERMASTERRESETPRINTERCONNECTORPRINTERFUSEPS2 PC KEYBOARDAD
The IR Keypad is typically the most convenient method to program the system. The sensor for the IRKeypad is just below the SOUND ALARMS button on the
Logging InTo enter programming mode you need to log in.The Main Panel must be powered up and must have initialized itself i.e. NOT be showing the‘INIT
Getting The System RunningEnsure all Sub-panels and Repeaters have unique addresses. Ensure all connectors are firmly in place.Ensure that all connect
Learning Which Devices Are FittedEnter programming mode.If site specific data has NOT been pre-programmed then select function 8-3-1 Clear Customer Fl
Sounder Audibility CheckIf the building is unoccupied then press SOUND ALARMS. All sounders should operate until the buttonis pressed again. Confirm t
Analogue Loop MonitoringOpen Circuit TestCheck that a short circuit or open circuit is detected on every Analogue Loop.Disconnect either the + or the
Conventional Sounder MonitoringCheck the Conventional Sounder circuits for open and short circuit fault detection.Main Panels and Repeaters with Integ
Detector TestsDetector Tests By ZoneUnassigned Detector TestsIf the devices have been assigned to Zones (on a pre-programmed SIM CARD or via theprogra
COMMISSIONINGThe Main Panel ButtonsIntroductionCommissioning involves checking that all connections have been made properly and that allhardware is fu
Wrapping Up Installation And CommissioningAt this stage you may program the more advanced features of the system. The basic minimum usuallyinvolves as
Master ResetA Master Reset is not accessed through the programming menus. It occurs automatically when theMain Panel power is cycled (both primary and
L0285DSERIES 4000MAIN TERMINAL BOARD24VOUTPUTPSU 24VINPUT+Ve -Ve-Ve+VeCF0V+24AUXILIARYNOWNCFAULTNOWNCEVAC.SOUNDERS- +2- +12NOWNC1NOWNCFIRE AUXILIARYLO
Title: Client: Drg. No.Drn: Date: Checked: Approved:NCRDRWACBA4000 - 021Iss.UNIT 14 , MERIDIAN CTR , VULCAN WAYSURREY , CROYDON , CR0 9UGTEL : 01689 8
ALARM SILENCESYSTEM RESETLAMP TESTSOUND ALARMSIf a fire has been detected and the sounders are operating this button will silence the sounders. TheLED
ACTIVE DELAYSFIRE (QUEUE REVIEW)FAULT (QUEUE REVIEW)TEST (QUEUE REVIEW)DISABLED (QUEUE REVIEW)Only when this button is activated (and the button LED i
Getting The Main Panel RunningIf you have the optional printer fitted make sure that the printer paper is not being held firm by anelastic band or pie
Getting A Repeater RunningNote that if the Main Panel is not powered up the Repeater WILL report a communication fault when itis powered up. This is e
Getting A Standard Sub-panel RunningIf the Standard Sub-panel is fitted within the Main Panel or Repeater box and wired up correctly thenthe green COM
Setting Panel Addresses And TypesEach Repeater and Sub-panel needs a unique address.Each Repeater and Sub-panel also needs the detector type set.This
1 2 3 4 5 6ONBATT24VEVACPA NE L N OSILENCEAMPXCN5H8/3003Standard Sub-panelsThe Standard Sub-panel addresses and detector types are set using the DIP s